12.8 H: Terminal Functions
838 YASKAWA SIEPC71061705H GA700 Series Technical Manual
Figure 12.102 Reverse Operation Output Time Chart
■ 1B: During Baseblock (N.C.)
Setting Value Function Description
1B During Baseblock (N.C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does
not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
■ 1C: Motor 2 Selected
Setting Value Function Description
1C Motor 2 Selected
The terminal activates when you select motor 2.
ON : Motor 2 Selected
OFF : Motor 1 Selected
■ 1D: During Regeneration
Setting Value Function Description
1D During Regeneration
The terminal activates on when the motor is regenerating.
ON : Motor is regenerating.
OFF : Motor is operating or stopped.
■ 1E: Executing Auto-Restart
Setting Value Function Description
1E Executing Auto-Restart
The terminal activates when the Auto Restart function is trying to restart after a fault.
The terminal deactivates when the Auto Restart function automatically resets a fault. The terminal deactivates
when the Auto Restart function detects the fault again because there were too many restart attempts as specified
by L5-01 [Number of Auto Restart Attempts].
Note:
Refer to L5: Fault Restart on page 897 for more information.
■ 1F: Motor Overload Alarm (oL1)
Setting Value Function Description
1F Motor Overload Alarm
(oL1)
The terminal activates when the electronic thermal protection value of the motor overload protective function is a minimum of
90% of the detection level.
Note:
Refer to “L1-01: Motor Overload (oL1) Protection” for more information.