12.8 H: Terminal Functions
870 YASKAWA SIEPC71061705H GA700 Series Technical Manual
2 : 0 to 100% (Lower Limit at 0)
H7-41: Virtual Analog Output Function
No.
(Hex.)
Name Description
Default
(Range)
H7-41
(1164)
Virtual Analog Output
Function
Sets the monitor to be output from the virtual analog output.
102
(0 - 999)
Set the x-xx part of the Ux-xx [Monitor]. For example, set H7-41 = 102 to monitor U1-02 [Output Frequency].
H7-42: Virtual Analog Output FilterTime
No.
(Hex.)
Name Description
Default
(Range)
H7-42
(1165)
Virtual Analog Output
FilterTime
Sets the time constant for a primary filter of the virtual analog output.
0.00 s
(0.00 - 2.00 s)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV