12.9 L: Protection Functions
904 YASKAWA SIEPC71061705H GA700 Series Technical Manual
1 : oL @ Speed Agree - Alarm only
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs an oL4 [Overtorque Detection 2] and operation
continues.
2 : oL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an oL4 and
operation continues.
3 : oL @ Speed Agree - Fault
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs an oL4 [Overtorque Detection 2] and operation stops.
4 : oL @ RUN - Fault
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an oL4 and
operation stops.
5 : UL @ Speed Agree - Alarm only
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a UL4 [Undertorque Detection 2] and operation
continues.
6 : UL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a UL4 and
operation continues.
7 : UL @ Speed Agree - Fault
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a UL4 and operation stops.
8 : UL @ RUN - Fault
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a UL4 and
operation stops
■ L6-05: Torque Detection Level 2
No.
(Hex.)
Name Description
Default
(Range)
L6-05
(04A5)
Torque Detection Level 2
Sets the detection level for Overtorque/Undertorque Detection 2. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
150%
(0 - 300%)
Note:
Overtorque/Undertorque Detection 2 cannot set the detection level for the analog input terminal.
■ L6-06: Torque Detection Time 2
No.
(Hex.)
Name Description
Default
(Range)
L6-06
(04A6)
Torque Detection Time 2
Sets the detection time for Overtorque/Undertorque Detection 2.
0.1 s
(0.0 - 10.0 s)
■ L6-07: Torque Detection Filter Time
No.
(Hex.)
Name Description
Default
(Range)
L6-07
(04E5)
Torque Detection Filter
Time
Sets the time constant for a primary filter to the torque reference or to the output current used to
detect overtorque/undertorque.
0 ms
(0 - 1000 ms)
■ L6-08: Mechanical Fatigue Detect Select
No.
(Hex.)
Name Description
Default
(Range)
L6-08
(0468)
Mechanical Fatigue Detect
Select
Sets the speed where the drive detects mechanical deterioration and how the drive operates
(operation status) after detection.
0
(0 - 8)