12.12 T: Auto-Tuning
970 YASKAWA SIEPC71061705H GA700 Series Technical Manual
■ T4-06: Motor Rated Voltage
No.
(Hex.)
Name Description
Default
(Range)
T4-06
(3135)
Motor Rated Voltage
Sets the rated voltage (V) of the motor.
200 V Class: 200.0 V,
400 V Class: 400.0 V
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■ T4-07: Motor Rated Current
No.
(Hex.)
Name Description
Default
(Range)
T4-07
(3136)
Motor Rated Current
Sets the rated current (A) of the motor.
Determined by o2-04, C6-
01
(10% to 200% of the drive
rated current)
Note:
The value set here becomes the base value for motor protection, the torque limit, and torque control.
■ T4-08: Motor Rated Capacity
No.
(Hex.)
Name Description
Default
(Range)
T4-08
(3137)
Motor Rated Capacity
Sets the motor rated power in the units set in o1-58 [Motor Power Unit Selection].
Determined by E9-10
(0.10 - 650.00 kW)
■ T4-09: Number of Poles
No.
(Hex.)
Name Description
Default
(Range)
T4-09
(3138)
Number of Poles
Sets the number of motor poles.
Determined by E9-01
(2 - 120)