ECODRIVE03-FL*-04VRS Parameters 9-39
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
B008 Analog Output 2, Scaling per 10V Full Scale
00001.0000
Scaling / Bit Number
The resolution of the selected signal can be varied using Parameter
B008, Analog Output 2 Scaling per 10V Full Scale. If a signal number
is assigned via B006, Analog Output 1, Signal Selection, scaling
always uses the same unit as the parameter with the assigned ID
number.
When pre-defined signals are output, scaling is defined as a factor having
4 decimal places. It has a permanent reference with a fixed unit. The
scaling defines the least significant bit for bit and byte output. The input is
an integer value without decimal places.
B009 Serial I/O Control for BTV04
0 200
maximum cycle time [ms] (200-500 ms)
0 no serial inputs/outputs active
1 serial inputs/outputs active
The system reads the X4 inputs and writes to the X5 outputs on the
BTV04 via the serial interface. The transmission rate depends on the type
of transmission and the baud rate. Cyclic transmission is monitored by the
control unit. If no new message is received within the maximum cycle
time, the control unit generates the following warning or error message:
"E- 01 05 Serial I/O offline"
"F- 03 17 Serial I/O Error"
The following can be transmitted:
11 Inputs I1.03.0 to I1.04.1
12 Outputs Q1.03.0 to Q1.04.2
10 Keys I1.00.0 / I1.00.1 and I1.01.0 to I1.01.7
Note: The BTV04 inputs and outputs can only be accessed with
Adress 5 when using the BTV04 and FWA-BTV04*-ELC
firmware!
Note: If only the X4 inputs are used, the zero potentional for the
inputs on connector X5/12 must be conrected!