ECODRIVE03-FL*-04VRS Diagnostic Message Descriptions 12-53
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
F- 0212 Program run without power
Power is not on!
In Automatic Mode, a start is triggered without the power being turned
on.
While the program is running in Automatic Mode, the power was
switched off.
F- 0213 Measuring Wheel Difference
When Measuring Wheel Mode is active, the slip between the motor
encoder and the measuring wheel encoder is greater than the monitoring
window set in the parameters. See Parameter A117, Encoder Difference
Monitoring.
F- 0214 Wrong BCD information
The bit pattern for the programmed bits is not in BCD-F format for:
BIC command
CVT command: changes in bit pattern according to variable
F- 0215 FOL Factor > Max.
The value of the slave factor in the FOL command is greater than
99.999999.
Cause:
For constants: Data loss.
For variables: Value of the destination variable is too large.
Possibly caused by access to an incorrect
destination variable when using indexed
variables.
Remedy:
Re-save the command with valid values.
F- 0216 V > 999 Per Mil
The value for the velocity in the commands CON, POA, POI, PFA, PFI,
PSA, PSI, SRM, VCC or VMC is greater than 999 per mil.
Cause:
For constants: Data loss.
For variables: Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
Remedy:
Re-save the command with valid values.