12-58 Diagnostic Message Descriptions ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
F- 0308 AT Failure
The initialization of communication between the drive and NC is not o.k.
Cause:
Data loss.
Firmware update was executed. Previously, a different firmware or a
different version was loaded.
Remedy:
If possible, pre-select Parameter Mode and clear the error message.
Using S1, S2, and S3 on the programming module, execute a Load
parameters with default values. (See Chapter 4 S1 Key on Programming
Module.)
If the error continues to occur:
Please contact REXROTH Customer Service. Explain precisely under
what circumstances the error occurred. The firmware should be replaced.
F- 0309 NC cycle error
The initialization of communication between the drive and NC is not o.k.
Cause:
Data loss.
Firmware update was executed. Previously, a different firmware or a
different version was loaded.
Remedy:
If possible, pre-select Parameter Mode and clear the error message.
Using S1, S2, and S3 on the programming module, execute a Load
parameters with default values. (See Chapter 4 S1 Key on Programming
Module.)
If the error continues to occur:
Please contact REXROTH Customer Service. Explain precisely under
what circumstances the error occurred. The firmware should be replaced.
F- 0310 Parameter error
1. A parameter contains invalid data.
2. The contents of a parameter element is too large or too small.
3. The contents of a combination of parameters is not permitted.
Incorrect parameter combinations:
A100: The motion type continuous or rotary table is
programmed and in Parameter CM00, a linear motor is
pre-selected.
A107: The setup velocity is greater than A106 Maximum
Velocity.
A111: The switching threshold is greater than A105 Modulo
Value for A100 Motion Type Rotary Table.
AA19: The timeout duration is set in the parameters, but the
press function is not activated in AA12.
B009: Serial inputs/outputs are set in the parameters, but no
SIS protocol is pre-selected in B002.