ECODRIVE03-FL*-04VRS Diagnostic Message Descriptions 12-55
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
F- 0222 SA1 not allowed
The output of an analog value with the SA1 command via the analog
channel AK1 is not possible, because the channel was already set for one
output signal of the drive. See Parameters B003 to B005.
Remedy:
Use either the ’SA1’ command or the analog output of the drive.
F- 0223 Wrong variable index
In an NC command, an indexed variable (V500...V507, V510...V517) is
programmed. However, an invalid variable is accessed.
Cause:
The variables ’Offset Factor’ and/or ’Variable Index’ are incorrect. The
following formulas must be followed:
[][][]
()
999 508*50950 600 ≤+≤ VVxV
[][][]
()
999 518*51951 600 ≤+≤ VVxV
L: [ ] Contents
L: [V50x] = Contents of V500 – V507
L: [V51x] = Contents of V510 – V517
Fig. 12-8: Limits for indexed variable access
See Chapter 6 ’Indexed Variables.’
F- 0224 APZ not allowed
Using the ’APZ’ command is not permitted, because Parameter AA11 is
not correctly set.
F- 0225 No curve data
For processing an NC function with cams (activation using the ’CSY’
command), required data like stroke, angle range or curve shape are still
missing. These data must be available to the function before activation.
Cause:
The required commands ’CMM,’ ’CLG’ and ’CAN’ were not called in the
’CSY’ command before activation.
F- 0226 Control signal bit 1 fault
The function was activated in Parameters AA14 and AA15, to compare
PLS positions with a particular state of an input signal. The state of the
input signal from Parameter AA15 did not correspond to the PLS position.
Check input signal and PLSs.