EasyManua.ls Logo

Bosch Rexroth OptiFeed-FS EcoDrive 03 FLP04VRS - 10 Interface; 10.1 Inputs; Outputs; Marker Flags

Bosch Rexroth OptiFeed-FS EcoDrive 03 FLP04VRS
490 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ECODRIVE03-FL*-04VRS Interface 10-1
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
10 Interface
10.1 Inputs / Outputs / Marker Flags
Designation
The designation of the inputs, outputs and marker flags.
M2.02.0
M = Marker Flag
I = Input
Q = Output
Bit
Byte
Source
Fig. 10-1: Structure of the Inputs / Outputs / Marker Flags
e.g.
I0.00.6
I Input
I0 Input, Connector X210
I0.00 Input, Connector X210, Group 0 (Byte 00)
I0.00.6 Input, Connector X210, Group 0 (Byte 00, Bit 6)
First user-programmable input
Inputs
The inputs are designated with I. They can be programmed and
processed in the parameters, commands, and in the Logic Task. They
are read at the beginning of each cycle (every 2 ms) or at the start of the
Logic Task.
Source Bytes Functions
0 00...01 DSUB Connector X210 DKC21.3
1 00...04 BTV04 (can be enabled via Parameter B009 / B010)
2 00...05 Fieldbus : Profibus DKC3.3
3 00...03 EMD Enhancement
4 00. .01 Hardware Inputs X1, X3
Fig. 10-2: Source Numbers of the Inputs

Table of Contents

Related product manuals