12-52 Diagnostic Message Descriptions ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
F- 0207 Invalid destination task number
The number of the destination task in the JTK command is not within the
range 1 to 3.
F- 0208 Per mil value in ACC command > 999
The value for acceleration and/or deceleration is greater than 999 per mil.
Cause:
For constants: Data loss.
For variables: Value of the destination variable is too large.
Possibly caused by access to an incorrect
destination variable when using indexed
variables.
Remedy:
Re-save the command with valid values.
F- 0209 Invalid value in FAK command
The value for the multiplication factor in the FAK command is not within
the range 0 to +1.999999.
Cause:
For constants: Data loss.
For variables: Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
Remedy:
Re-save the command with valid values.
F- 0210 Feed angle loss
The signal at the input Feed angle monitoring dropped off during a move.
See Parameter A116.
F- 0211 Torque > 500%
The value for at least one torque value in the MOM command is greater
than 500 percent.
Cause:
For constants: Data loss.
For variables: Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
Remedy:
Re-save the command with valid values.