ECODRIVE03-FL*-04VRS Diagnostic Message Descriptions 12-59
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
B009:No Serial inputs/outputs are set in the parameters, but
serial system control is pre-selected in B010.
B014: No EMD modules are set in the parameters, but system
control via EMD module is pre-selected in B010.
C011: The reference distance is greater than A105 Modulo
Value for A100 Motion Type Rotary Table.
C006: The timeout duration is set in the parameters, but the
press function is not activated in AA12.
F- 0311 Stack correction value > 9
The value for the correction of the subprogram stack level in the CST
command is greater than 9.
Cause:
For constants: Data loss.
For variables: Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
Remedy:
Re-save the command with valid values.
F- 0312 Select Parameter Mode
The error message "F- 03 10 Parameter Error was acknowledged.
Parameter Mode was not pre-selected.
Remedy:
Activate Parameter Mode and clear the error again. Then correct the
incorrect parameters.
F- 0313 Jump interval > 99
The value for the jump interval in the 'BIC' command is greater than 99.
Cause:
For constants: Data loss.
For variables: Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
Remedy:
Re-save the command with valid values.