ECODRIVE03-FL*-04VRS Diagnostic Message Descriptions 12-59
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
• B009:No ’Serial inputs/outputs’ are set in the parameters, but
’serial system control’ is pre-selected in B010.
• B014: No ’EMD modules’ are set in the parameters, but ’system
control via EMD module’ is pre-selected in B010.
• C011: The reference distance is greater than A105 ’Modulo
Value’ for A100 Motion Type ’Rotary Table.’
• C006: The ’timeout duration’ is set in the parameters, but the
press function is not activated in AA12.
F- 0311 Stack correction value > 9
The value for the correction of the subprogram stack level in the ’CST’
command is greater than 9.
Cause:
• For constants: Data loss.
• For variables: Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
Remedy:
Re-save the command with valid values.
F- 0312 Select Parameter Mode
The error message "F- 03 10 – Parameter Error“ was acknowledged.
Parameter Mode was not pre-selected.
Remedy:
Activate Parameter Mode and clear the error again. Then correct the
incorrect parameters.
F- 0313 Jump interval > 99
The value for the jump interval in the 'BIC' command is greater than 99.
Cause:
• For constants: Data loss.
• For variables: Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
Remedy:
Re-save the command with valid values.