Setting Maximum Braking Time
The Maximum Braking time is used to monitor the braking time and
activate the motor holding brake if the theoretical braking time is
exceeded due to an error.
The motor holding brake is activated once the time (set in A119, Best
possible deceleration) since the start of the error reaction has elapsed.
Note: The value in A119, Best possible deceleration must be set
so that the drive can come safely to a standstill from the
maximum speed at the maximum moment of inertia and
greatest load forces.
CAUTION
If the value in A119, Best possible deceleration is set
too low, then the error reaction is terminated and the
motor holding brake is activated at a speed greater than
10 RPM. Over time, this will damage the brake !
Connecting the Motor Holding Brake
See also Project Planning Specifications ECODRIVE 03