ECODRIVE03-FL*-04VRS Diagnostic Message Descriptions 12-37
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
C221 Feedback 2 initializing error
Several checks are performed during the initialization of an optional
encoder. An error was detected during this process. This error may be:
an error reading the angle rectification data
an error copying the angle rectification data
interruption of communications with the encoder
an assembly error regarding the position of an initialization track
an error reading the analog signals of an initialization track
an error in the pointer length for the analog signals of an initialization
track
an invalid offset between the high- and low-resolution tracks
Error in the measurement system micro-controller
with DAG 1.2: error, external 24V set for SSI interface
Cause:
1. Defective opt. encoder cable
2. Defective encoder
3. Defective measurement system interface
Remedy:
For 1. Check opt. encoder cable.
For 2. Replace encoder.
For 3. Replace the measurement system interface (module).
C223 Input value for max. range too high
Cause:
An internal position resolution was set which no longer ensures correct
commutation of the motor.
Remedy:
Check parameters and make corrections.
Check for correct firmware.
Turn off and then on again. If this does not solve the problem:
Replace the unit.
C227 Modulo range error
Cause:
The modulo value entered is larger than half of the position display range
of the drive.
Remedy:
Select a smaller modulo value, Parameter A105.