ECODRIVE03-FL*-04VRS Diagnostic Message Descriptions 12-27
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
E288 Firmware update of EMD Module active
If the Firmware of the drive controller has been replaced and the
Firmware of the EMD module has changed, the Firmware is automatically
updated when progressing from phase 2 to phase 3. During this time
warning E288 is displayed.
Note: If an error occurs during the Firmware update, the message.
F288, Error during firmware update of EMD module is
displayed.
Cause:
The Firmware in the EMD module does not match the Firmware in the
drive controller.
Remedy:
After the Firmware update the warning is automatically cleared.
E289 Waiting for scan by EcoX Master
During the command to transition from Phase 3 to Phase 4, the EcoX
Slave is tested to determine whether or not it was scanned by the EcoX
Master. The warning is automatically reset after the scan takes place.
Cause:
1. The EcoX bus has not been parameterized in the EcoX slave and/or
master
2. The EcoX master is in phase 2
3. The EcoX bus is disturbed
4. The EcoX bus has not been correctly wired
5. The supply voltage of the EcoX slaves has been cut off
Remedy for:
1. Check parameterization(s)
2. Switch EcoX master to phase 3 or phase 4
3. Check the EcoX bus
4. Check the wiring of the EcoX bus
5. Check supply voltage of the EMD modules