12-60 Diagnostic Message Descriptions ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
F- 0314 Instruction offset greater than 999
The value for the instruction offset in the BIC command is greater than
999.
Cause:
For constants: Data loss.
For variables: Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
Remedy:
Re-save the command with valid values.
F- 0315 BCD selection incorrect
The value for the mode in the BIC command is not within the range 0 to
1.
F- 0316 Systemcontrol Error
The real-time communication to the Fieldbus / BTV04 is interrupted.
Cause:
System control via the fieldbus or via the BTV04 is interrupted in Manual
or Automatic Mode.
Remedy:
BTV04:
Check grounding of all cables on the DKC.
Ground BTV04 housing.
Use shielded cables (Motor / Serial Interface).
Increase maximum cycle time in Parameter B009.
Possibly reduce the Answer Delay Time value (Default = 4ms) in
the BTV04.
Fieldbus :
Ensure that the fieldbus card connector is correctly inserted.
Check the fieldbus cable for errors.
Check master.
F- 0317 Serial I/O Error
The cyclic communication to the Fieldbus / BTV04 is interrupted for:
BTV04: In Manual or Automatic Mode, and Standard system
control (B010), if only the serial inputs/outputs in
Parameter B009 are activated.
Fieldbus: In Automatic Mode with serial system control or via the
EMD module (Parameter B010).