4-2 General Instructions for Start-Up ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
Address
S3 S2
Function Parameter
B001
Parameter B002 Para.
B009
Para.
B010
9 0
ASCII-Protocol 9600 Baud NO Parity
(MotionManager)
09600 1 05 1 1 0 1 0 004 0 200 0
9 1
SIS-Protocol 9600 Baud EVEN Parity
( BTV04)
09600 2 05 0 1 0 0 0 000 0 200 0
9 2
RS on drive 9600 Baud No Parity
( DriveTOP possible)
09600 2 05 not
programmable
9 3
SIS Protocol 9600 Baud No Parity
(for BTV04, for Dolfi Firmware Upgrade))
09600 1 05 0 1 0 0 0 000 0 200 0
9 4
SIS Protocol 9600 Baud EVEN Parity
(BTV04 with BTV keys and BTV I/O)
09600 2 05 0 1 0 0 0 000 1 200 1
temporary
9 5
SIS Protocol 9600 Baud EVEN Parity
(BTV04 with BTV keys and BTV I/O)
09600 1 05 0 1 0 0 0 000 1 200 1
9 7
Load parameter with default values
Programs, Variables, Marker Flags are cleared
SIS Protocol 9600 Baud NO Parity (BTV04)
09600 1 05 0 1 0 0 0 000 0 200 0
9 8
Load parameter with default values
ASCII Protocol 9600 Baud NO Parity
(MotionManager)
09600 1 05 1 1 0 1 0 004 0 200 0
Default
9 9
Load parameter with default values
SIS Protocol 9600 Baud NO Parity (BTV04)
09600 1 05 0 1 0 0 0 000 0 200 0
Fig. 4-1: Interface Settings Using the S2/S3 Switches
All functions will set the serial interface to 1 stopbit.
Diagnostic "E- 01 09" is issued at address 97, 98 or 99.
Note: The "temporarily" set interface parameters are reset to the
parameter values (B001/B002/B009/B010) after an error is
cleared or after exiting Parameter Mode.
Data Storage
Non-Volatile Memory
Various non-volatile data storage registers are contained in the drive.
The following operating data are stored there:
• configuration setting
• parameters
• programs
• stored marker flags and variables
• The data are stored to the corresponding operating data after each
instance of write access.
The following modules contain non-volatile memory:
• drive controller
• motor encoder (optional)
• programming module
• plug-in module (Profibus card, DIO card)