ECODRIVE03-FL*-04VRS Diagnostic Message Descriptions 12-41
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
C701 Basic load not possible with drive enable
Cause:
Basic load cannot be executed if the drive enable function is set.
Remedy:
1. Turn off drive enable.
2. Reinitiate command.
See also functional description for: "Causes of error in executing the
Basic load function"
C702 Default parameters not available
With motors of the MHD, MKD and MKE series, the control loops are
adapted to the connected digital drive by activating the speed controller
parameters stored in the motor feedback memory. Via message C702,
the drive controller signals that Basic load has been activated;
however, no data memory is present in the connected motor.
Remedy:
Order the parameter sheet for the motor from REXROTH Customer
Service, and enter the parameters.
C703 Default parameters invalid
Cause:
The default parameters are read from the motor feedback memory. At
least one of these parameters is invalid.
Remedy:
Check the connection to the motor feedback memory. Replace the motor
if necessary.
C704 Parameters not copyable
Cause:
The existing default parameters are not compatible with this software
version.
Remedy:
Please contact Rexroth. Explain which software version, which device and
which motor type you have.
C705 Locked with password
Set default parameters.