15-14 EMD Module (EcoX-Bus) ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
Position of Connections
ek5044F1_AE.WMF
Fig. 15-14: Position of Connections
Power Supply, Protection and Grounding
Power Supply
The input/output module must be supplied with 24 Volts DC power using
the clamps labeled as "unit supply" in Fig 15-14:
Green clamp: Grounding
Red clamp: 24 Volts
Blue clamp: 0 Volts
With the appropriate layout, the external power supply can be used as the
power source that is also used to supply the drive controller.
The actors (digital outputs) can be supplied in two ways:
via the unit supply
externally
Power for the sensors is supplied via the unit supply.