12-64 Diagnostic Message Descriptions ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
E- 0106 Jog, Position < Limit
Reverse jogging is not possible. The negative position limit value has
been reached or exceeded.
Remedy:
Move the axis with the signal jog forward into the motion range.
E- 0107 Jog, Position > Limit
Forward jogging is not possible. The positive position limit value has
been reached or exceeded.
Remedy:
Move the axis with the signal jog reverse into the motion range.
E- 0108 IDS01 Timeout
The Interface to the IDS-01 decade switch is interrupted.
Cause:
IDS-01 Power Supply.
Cable Connection.
Parameter settings for the Interface.
E- 0109 Load default values
Default values are loaded. Triggered by S1 probe with the Address 97-99
or via an interface command.
E- 0110 Jog, no power
In Manual Mode, one of the inputs Jog forward or Jog reverse was
applied when the power was off.