4-14 General Instructions for Start-Up ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
Error Message in the Firmware Loader
If a firmware update is performed via the serial interface (using the SIS
protocol), it is possible that the drive will generate error messages.
These messages are displayed both by DOLFI, as shown in the figure
below, and by the drive on its 7-segment display:
Dolfi_FLx_AE.bmp
Fig. 4-7: Example: An illustration of a Firmware was cleared error
The table below lists the error messages:
SIS Error
Message
Number
7 Segment
Display Error Message:
0x9002 dL / 00 Firmware was cleared
0x9003 - Loading not allowed in phase 3.
0x9004 - Loading not allowed in phase 4.
0x9102 dL / 03 Firmware was cleared
0x9103 - Restart not allowed in phase 3
0x9104 - Restart not allowed in phase 4
0x9200 dL / 06 Read error
0x9400 dL / 07 Timeout during delete
0x9402 dL / 0F Address range not in flash memory
0x940A dL / 08 Deletion possible only in loader
0x960A - Programming possible only in loader
0x96E0 dL / 0b Error during flash memory verification
0x96E1 dL / 0C Timeout when programming flash memory
0x96FF dL / 09 Error when writing to RAM
0x9701 dL / 0d Wrong checksum
0x9702 dL / 0E Wrong CRC32 checksum
Fig. 4-8: SIS Errors in the Firmware Loader