12-56 Diagnostic Message Descriptions ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
F- 0227 Control signal bit 2 fault
The function was activated in Parameters AA14 and AA16, to compare
PLS positions with a particular state of an input signal. The state of the
input signal from Parameter AA16 did not correspond to the PLS position.
Check input signal and PLSs.
F- 0228 Control signal bit 3 fault
The function was activated in Parameters AA14 and AA17, to compare
PLS positions with a particular state of an input signal. The state of the
input signal from Parameter AA17 did not correspond to the PLS position.
Check input signal and PLSs.
F- 0229 Control signal bit 4 fault
The function was activated in Parameters AA14 and AA18, to compare
PLS positions with a particular state of an input signal. The state of the
input signal from Parameter AA18 did not correspond to the PLS position.
Check input signal and PLSs.
F- 0230 Offset dimension too small
The offset dimension in the ’LAR’ command is too small. It must be longer
than twice the distance:
• A106
2
/ (2*A109)
• resp. indicated in the ’CLG’ command
F- 0300 Invalid I/O number in command instruction
Cause:
An NC command for setting one (or more) output bit(s) uses an output bit
that has already been occupied by a parameter or the Logic Task. Double
assignment of output bits in the NC program, Logic Task or parameters is
not possible.
Remedy:
Use a different available output bit.
F- 0301 I/O status illegal
The bit status indicated in the ’AEA,’ ’AKN’ or ’BCE’ command is not ’0’ or
’1.’
Cause:
• Wrong variable content.
• Data error.