9-60 Parameters ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
9.7 Motor Parameters
CM00 Motor Type
5
Motor Type
The motor type can be selected with this parameter. The following motor
types are supported:
1: MHD
2: Not allowed (2AD / 1MB with NTC temperature sensor)
3: LSF
4: LAR / LAF
5: MKD / MKE
6: Not allowed (2AD / 1MB with PTC temperature sensor)
7: Synchronous kit motor
Input min.: 1
Input max.: 7
CM01 Bipolar Torque/Force Limit Value
400
[%]
This parameter specifies the maximum permissible torque and applies
symmetrically in both directions. It ensures that the maximum permissible
peak torque for the given application is not exceeded, regardless of how
high the torque/force is set in the MOM command.
The evaluation is based on the percentage of the motor current at
standstill:
Input min.: 1 %
Input max.: 500 %