15-4 EMD Module (EcoX-Bus) ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
Outputs
Number 16
Connections triple-conductor
External Power Supply
total
by group
with power supply clamps 24 V, 0 V
and ground clamp
with power supply clamps for each
group of 8 outputs
Rated Voltage U
B
V [DC] 24
Rated Current
maximum per output
maximum per group
maximum per module (16 DO)
I
B
A
0.5
4.0
8.0
Leakage Current mA < 0.2
Maximum Switching Frequency
with Ohm load
with inductive load
Short-Circuit Diagnostic no short-circuit diagnostic possible
Short-Circuit Protection electronic, automatic re-start
Electronic Isolation – Circuit Side no
Conditions for Use
Ambient Temperature Allowed °C0° ... +55°
Storage and Transport Temperature °C-25° ... +70°
max. m over NN 2000
Max. Allowable Relative Humidity % 10 - 45, no condensation
Air Pressure during Operation hPa 86 ... 106
Protection Type IP 20 according to EN 60529
/IEC 529
Special Requirements for Operation The unit can be used in locations
where dust, caustic steam, caustic
gases or ionized radiation can be
present, only if additional measures
are undertaken!
Fig. 15-5: EMD Input/Output Module Data