16-2 IDS Accessories ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
Die IDS1.1 operates with the following transmission parameters:
RS232, 2400 Baud, 1 Start Bit, 8 Data Bits, 1 Stop Bit, no parity check.
A timeout is effective in Automatic Mode. If more than 2 seconds pass
without receiving a valid IDS1.1 telegram, the following message is
displayed: "E- 01 08 IDS01 timeout." Any positioning function in
process is terminated and the NC user program is subsequently
stopped.
B002, Protocol Parameter Mode Manual Mode Automatic Mode
0 SIS SIS SIS
1 ASCII ASCII ASCII
2SIS
IDS IDS
3 ASCII
IDS IDS
Fig. 16-3: B002, Protocol Setting
The IDS information that has been read is made available in system
variables V015 to V018 and can be accessed there by the user NC
program.
The distance between the DKC and the IDS1.1 can be up to 15 m. If
power is available directly on the IDS, longer cables can sometimes be
used.
IDS_Hard_TYP_AE.WMF
Fig. 16-4: IDS Typecode