Chapter 15 Tips/FAQ/Troubleshooting
15-4-5
S8: Torque is not generated
Exemplar measures to be taken
Inadequate parameters are
used and acceleration torque
is not sufficient.
Set the torque boost or switch to sensorless vector control
and adjust parameters.
The inverter is used for
lowering.
If torque is insufficient in regenerative operation, perform
the following adjustment.
- Increase the deceleration time.
- Set "AVR function selection [A081]
*1
" to "Disable (01)".
- Use a braking resistor or regenerative braking unit.
It may be necessary to review the capacity of both the
motor and inverter.
S9: Parameters to be set are not displayed
Exemplar measures to be taken
Display restriction has been
set.
The display restriction function may be activated. Review
"Display restriction selection [b037]".
If [b037] cannot be changed, the password function may
be working. If that case, cancel the password.
When the "Display lock [DISP]" input terminal is ON, keypad
operation cannot be accepted. If that case, turn off the
[DISP] terminal.
S10: Keypad cannot be operated or parameters cannot be set
Exemplar measures to be taken
When the "Display lock [DISP]" input terminal is ON, keypad
operation cannot be accepted. If that case, turn off the
[DISP] terminal.
Some parameters cannot be changed during running. If it
cannot be changed, stop the inverter once.
Disable Soft-Lock function.
The setting range of the
parameter, etc. has changed
due to the change of the
inverter mode or load type
setting.
By changing the "Load type selection [b049]" and "Inverter
mode selection [b171]", the setting range of some
parameters are changed and some parameters are hidden.
The current mode setting can be checked on the "Inverter
mode monitor [d060]". If the mode is not intended, change
the mode.