Chapter 18 List of Parameters/Modbus Coil/Register Numbers
18-2-6
Code
Name
Data range
Initial
value
Set
value
Change
during
running
Modbus communication
Page
Register No.
Data Range
Resolution
A020
Multi-speed 0,
1st-motor
0.00, Minimum frequency to
Maximum frequency, 1st-
motor (Hz)
0.00/
6.00/
0.00
*2
✓
1216h (High)
1217h (Low)
0, Minimum
frequency to
Maximum
frequency,
1st-motor
0.01
9-2-7
A220
Multi-speed 0,
2nd-motor
0.00, Minimum frequency to
Maximum frequency, 2nd-
motor (Hz)
✓
2216h (High)
2217h (Low)
0, Minimum
frequency to
Maximum
frequency,
2nd-motor
0.01
A021
Multi-speed 1
0.00, Minimum frequency to
Maximum frequency (Hz)
0.00
✓
1218h (High)
1219h (Low)
0, Minimum
frequency to
Maximum
frequency
0.01
A022
Multi-speed 2
✓
121Ah (High)
121Bh (Low)
A023
Multi-speed 3
✓
121Ch (High)
121Dh (Low)
A024
Multi-speed 4
✓
121Eh (High)
121Fh (Low)
A025
Multi-speed 5
✓
1220h (High)
1221h (Low)
A026
Multi-speed 6
✓
1222h (High)
1223h (Low)
A027
Multi-speed 7
✓
1224h (High)
1225h (Low)
A028
Multi-speed 8
✓
1226h (High)
1227h (Low)
A029
Multi-speed 9
✓
1228h (High)
1229h (Low)
A030
Multi-speed 10
✓
122Ah (High)
122Bh (Low)
A031
Multi-speed 11
✓
122Ch (High)
122Dh (Low)
A032
Multi-speed 12
✓
122Eh (High)
122Fh (Low)
A033
Multi-speed 13
✓
1230h (High)
1231h (Low)
A034
Multi-speed 14
✓
1232h (High)
1233h (Low)
A035
Multi-speed 15
✓
1234h (High)
1235h (Low)
A038
Jogging
frequency
Minimum frequency to 10.00
(Hz) (100.00 (Hz))
*3
6.00
✓
1238h
Minimum
frequency
adjustment to
1000 (10000)
*3
0.01
9-2-10
A039
Jogging stop
mode selection
00: Free run at Jogging stop
(Disable at run)
01: Deceleration stop at
Jogging stop (Disable at
run)
02: DC braking at Jogging
stop (Disable at run)
03: Free run at Jogging stop
(Enable at run)
04: Deceleration stop at
Jogging stop (Enable at
run)
DC braking at Jogging stop
(Enable at run)
04
✓
1239h
0 to 5
-
A041
Torque boost
mode selection,
1st-motor
00: Manual torque boost
01: Automatic torque boost
00
×
123Bh
0 to 1
-
9-5-5
A241
Torque boost
mode selection,
2nd-motor
00: Manual torque boost
01: Automatic torque boost
00
×
223Bh
0 to 1
-
*2. The default settings when initialize by setting 00/01/03 to "Initialize data selection [b085]".
*3. When in WJ200 high frequency compatible mode.