EasyManua.ls Logo

Hitachi WJ C1 Series

Hitachi WJ C1 Series
494 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 18 List of Parameters/Modbus Coil/Register Numbers
18-2-7
Code
Name
Data range
Initial
value
Set
value
Change
during
running
Modbus communication
Page
Register No.
Data Range
Resolution
P126
EzSQ user
parameter U(26)
0 to 65535
0
1680h
0 to 65535
1
12-2-3
P127
EzSQ user
parameter U(27)
0 to 65535
0
1681h
0 to 65535
1
P128
EzSQ user
parameter U(28)
0 to 65535
0
1682h
0 to 65535
1
P129
EzSQ user
parameter U(29)
0 to 65535
0
1683h
0 to 65535
1
P130
EzSQ user
parameter U(30)
0 to 65535
0
1684h
0 to 65535
1
P131
EzSQ user
parameter U(31)
0 to 65535
0
1685h
0 to 65535
1
P140
EzCOM number of
data
1 to 5
5
168Eh
1 to 5
1
11-4-2
P141
EzCOM destination
address 1
1 to 247
1
168Fh
1 to 247
1
P142
EzCOM destination
register 1
0000h to FFFFh
0000
1690h
0000h to
FFFFh
1
P143
EzCOM source
register 1
0000h to FFFFh
0000
1691h
0000h to
FFFFh
1
P144
EzCOM destination
address 2
1 to 247
2
1692h
1 to 247
1
P145
EzCOM destination
register 2
0000h to FFFFh
0000
1693h
0000h to
FFFFh
1
P146
EzCOM source
register 2
0000h to FFFFh
0000
1694h
0000h to
FFFFh
1
P147
EzCOM destination
address 3
1 to 247
3
1695h
1 to 247
1
P148
EzCOM destination
register 3
0000h to FFFFh
0000
1696h
0000h to
FFFFh
1
P149
EzCOM source
register 3
0000h to FFFFh
0000
1697h
0000h to
FFFFh
1
P150
EzCOM destination
address 4
1 to 247
4
1698h
1 to 247
1
P151
EzCOM destination
register 4
0000h to FFFFh
0000
1699h
0000h to
FFFFh
1
P152
EzCOM source
register 4
0000h to FFFFh
0000
169Ah
0000h to
FFFFh
1
P153
EzCOM destination
address 5
1 to 247
5
169Bh
1 to 247
1
P154
EzCOM destination
register 5
0000h to FFFFh
0000
169Ch
0000h to
FFFFh
1
P155
EzCOM source
register 5
0000h to FFFFh
0000
169Dh
0000h to
FFFFh
1
P160
Flexible command
writing register 1
0000h to FFFFh
0000
16A2h
0000h to
FFFFh
1
13-2-2
P161
Flexible command
writing register 2
0000h to FFFFh
0000
16A3h
0000h to
FFFFh
1
P162
Flexible command
writing register 3
0000h to FFFFh
0000
16A4h
0000h to
FFFFh
1
P163
Flexible command
writing register 4
0000h to FFFFh
0000
16A5h
0000h to
FFFFh
1
P164
Flexible command
writing register 5
0000h to FFFFh
0000
16A6h
0000h to
FFFFh
1
P165
Flexible command
writing register 6
0000h to FFFFh
0000
16A7h
0000h to
FFFFh
1
P166
Flexible command
writing register 7
0000h to FFFFh
0000
16A8h
0000h to
FFFFh
1
P167
Flexible command
writing register 8
0000h to FFFFh
0000
16A9h
0000h to
FFFFh
1
P168
Flexible command
writing register 9
0000h to FFFFh
0000
16AAh
0000h to
FFFFh
1
P169
Flexible command
writing register 10
0000h to FFFFh
0000
16ABh
0000h to
FFFFh
1
P170
Flexible command
reading register 1
0000h to FFFFh
0000
16ACh
0000h to
FFFFh
1
P171
Flexible command
reading register 2
0000h to FFFFh
0000
16ADh
0000h to
FFFFh
1
P172
Flexible command
reading register 3
0000h to FFFFh
0000
16AEh
0000h to
FFFFh
1

Table of Contents