Commissioning
5-22
L
EDSVS9332P-C EN 3.0
5.9 Load parameter set
5.9.1 Load parameter set from the PC
The operating menu (Fig. 5-17) enables the parameter set to be loaded
from the hard disk of the PC or a diskette in GDC by Read all parameter sets from file,
from the PC to the controller with Write current parameter set to the controller (F5).
Warning!
The controller is reinitialised by the parameter set transfer from the PC to the controller:
System configurations and terminal assignments can be changed. Make sure that your
wiring and drive configuration comply with the settings of the parameter set.
Use terminal X5/28 as source for the controller inhibit or the STOP function from GDC.
A parameter set can only be transferred with an inhibited controller.
1. Insert the floppy with the parameter set into the drive of the PC. Click on Drive parameters in
the menu bar of the GDC.
Fig. 5-17 Dialog box Read all parameter sets from file
2. Select Read all parameter sets from file.
3. Select the drive and the parameter set which is to be loaded. Confirm with OK.
4. Make sure that your wiring and drive configuration comply with the settings of the new
parameter set.