Commissioning
5-11
L
EDSVS9332P-C EN 3.0
5.6.5 Controller enable
•
The controller is only enabled if all sources of controller inhibit are reset.
– When the controller is enabled, the green LED on the controller is illuminated.
•
For displaying active sources of a controller inhibit see chapter ”Troubleshooting”
(E 8-1)
.
The following table shows the conditions for controller enable:
Source controller inhibit Controller inhibited Controller enabled Note
Terminal X5/28 0 V ... +4 V +13 V ... +30 V -
Fault In case of TRIP
In case of message
TRIP reset For c heck see
E 8-1
System bus (CAN) Transmission of control
information INHIBIT via C0135
Transmission of control
information ENABLE via C0135
E Manual
Fieldbus module See Operating Instructions for the corresponding fieldbus module -
Tip!
All sources of controller inhibit act like a series connection of switches that are independent of each
other.
Stop!
When the internal control structure is changed, another terminal assignment may result.