7.5.68.2 Ramp function generator
The setpoint PCTRL-SET is led by a ramp generator with linear characteristic.Thus, setpoint
step-changes at the input can be transformed into a ramp.
100%
0
t
ir
t
if
T
ir
T
if
t
RFG-OUT
[%]
w1
w2
T
ir
= t
ir
100%
w2 w1
T
if
= t
if
100%
w2 w1
Fig. 7-199 Acceleration and deceleration times of the ramp generator
The ramps can be adjusted separately for acceleration and deceleration.
Acceleration time t
ir
with C0332.
Deceleration time t
if
with C0333.
PCTRL-INACT = HIGH
The ramp generator is immediately set to zero.
7.5.68.3 Value range of the output signal
The process controller operates bipolar in the default setting.
The output value is limited to ±100 % .
The function can be set unipolar under C0337.
The output value is limited to 0 ... +100 %.
7.5.68.4 Evaluation of the output signal
The output signal can be evaluated after the limitation block via PCTRL-INFLU.
The process controller can be used or suppressed with this evaluation.
The calcuation is done according to the following formula:
100 % (PCTRL-OUT) = 100 % * 100 % (PCTRL-INFLU).
7.5.68.5 Deactivation of the process controller
PCTRL-INACT = HIGH deactivates the process controller
PCTRL-OUT is set to zero.
The I-component is set to zero.
The ramp generator is set to zero.