7.5.62 Monitor outputs of monitoring system (MONIT)
Purpose
The monitoring functions output digital monitor signals.
FB_monit
LU
OU
EER
..
..
..
..
P18
SD8
nErr
MONIT
Fig. 7-175 Monitor outputs of the monitoring system (MONIT)
Function
The MONIT-outputs switch to HIGH level if one of the monitoring functions responds.
The digital monitor signals respond dynamically, i.e.
depending on the state of the monitoring function, but
independent of the selected fault reaction (trip, fail-QSP, ...).
Example
MONIT-LP1 (motor phase monitoring) responds if a cable disruption is detected in a motor
connection phase, although the fault reaction of LP1 is set to Off (C0597 = 3).
Tip!
Only with a corresponding signal conditioning it is possible to use the MONIT-outputs to
detect the cause of malfunction afterwards (e.g. storing the signal by using function block
FLIP).
A detailed description concerning monitoring /fault messages can be found in the chapter
Troubleshooting and fault elimination.