Function library
7-193
L
EDSVS9332P-D21 EN 3.0
7.5.49 Freely assignable digital outputs (DIGOUT)
Purpose
Conditioning of the digital signals and output to the terminals X5/A1 to X5/A4.
A1
A2
A3
A4
1
0
C0118/1...4
DIGOUT
DIGOUT1
DIGOUT2
DIGOUT3
DIGOUT4
C0117/1
C0117/2
C0117/3
C0117/4
C0444/4
C0444/3
C0444/2
C0444/1
X5
1
Fig. 7-148 Freely assignable digital outputs (DIGOUT)
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
DIGOUT1 d C0444/1 bin C0117/1 2 15000 -
DIGOUT2 d C0444/2 bin C0117/2 2 10650 -
DIGOUT3 d C0444/3 bin C0117/3 2 500 -
DIGOUT4 d C0444/4 bin C0117/4 2 5003 -
Function
The terminals X5/A1 to X5/A4 are updated every millisecond. The level for every output can be
inverted. For this, proceed as follows:
Select code C0118 with corresponding subcode (e.g. subcode 3 for output X5/A3)
Enter the desired level as a parameter:
0 = Level not inverted (HIGH active)
1 = Level inverted (LOW active)