Commissioning
5-26
L
EDSVS9332P-C EN 3.0
5.10.3 Manual homing
The controller can perform all positioning tasks only with a defined reference point (zero point).
Click on the Control buttonintheBasic settings dialog box.
9300pos044
Fig. 5-20 Dialog box Control
Field
Command Function
1 Select ”Manual operation” Manual operation active
5 With drive status ”OK”, ”Start” is possible. E 6-2
4 Controller ”Start” Starts the controller if there is no interference.
2
Select ”Manual homing”. The drive uses the reference parameters for positioning. E 5-25
Reset ”Manual homing”. The drive stops.
Override the reference s witch. The drive traverses to the next zero position of the rotor and brakes to a standstill.
This position is now considered to be the reference point for all positioning data.
3
Status display ”Reference OK” is displayed a fter successful reference homing.
Terminal X5/ A4 = HIGH