7.6.3.11 Heatsink monitoring OH (fixed)
Purpose
Controller protection
MONIT
TEMP-COOLER
MONIT-OH
C0061
85 °C
Fig. 7-244 Heatsink monitoring OH
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
TEMP-COOLER - C0061 dec - - - cannot be reassi gned
MONIT-OH d - - - - - -
Function
The signal OH is derived from a comparator with hysteresis. The switch-off threshold is 85°Candis
fixed. The hysteresis is also fixed and amounts to 5K, i.e. the reclosing point is 80°C.
Features:
LECOM no.: 50
Reaction: TRIP (cannot be modified)
Tripping can have the following causes:
The ambient temperature is too high.
Remedy:
Install a fan into the switch cabinet.
The controller is overloaded in its arithmetic mean, i.e. overload and recovery phase exceed
100 %.
Remedy:
Reduce overload phase
Use more powerful controller