Function library
7-171
L
EDSVS9332P-D21 EN 3.0
7.5.42.4 TRIP-SET
The drive is controlled to the status set under code C0581 and indicates EEr (external error).
This function can be controlled via 4 inputs.
Control word CAN-CTRL bit 10 from CAN-IN1
Control word AIF-CTRL bit 10 from AIF-IN
Control word C0135 bit 10
Free input DCTRL-TRIP-SET
All inputs are OR linked.
C0136/1 indicates the control word C0135
7.5.42.5 TRIP-RESET
Resets an active trip after the cause has been eliminated. If the cause is still active, it does not
respond.
This function can be controlled via 4 inputs.
Control word CAN-CTRL bit 11 from CAN-IN1
Control word AIF-CTRL bit 11 from AIF-IN
Control word C0135 bit 11
Free input DCTRL-TRIP-RESET
All inputs are OR linked.
This function is only carried out by a LOW-HIGH transition of the signal resulting from the OR
linkage.
C0136/1 indicates the control word C0135
Note!
If one of the inputs is set to HIGH, it is not possible that a LOW-HIGH transition occurs at the resulting
signal.
7.5.42.6 Controller status
ThestatusisbinarycodedintheoutputDCTRL-STAT*x.
STAT*8 STAT*4 STAT*2 STAT*1 Controller action
0 0 0 0 Initialization after connectio n of the supply voltage
0 0 0 1 LOCK-MODE, restart protection active C0142
0 0 1 1 Drive is i nhibited
0 1 1 0 Controlle r enabled
0 1 1 1 The activation of a monitoring leads to a ’message’.
1 0 0 0 The release of a monitoring function resulted in a ”trip”
1 0 1 0 A monitoring function was activated and set ”FAIL-QSP