Configuration
7-306
L
EDSVS9332P-D21 EN 3.0
7.6.3.12 Motor temperature monitoring OH3 (fixed)
Purpose
Protects the motor from overheating
MONIT
TEMP-MOTOR
MONIT-OH3
C0063
150 °C
Fig. 7-245 Motor temperature monitoring OH3 with fixed threshold
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
TEMP-MOTOR - C0063 dec - - - -
MONIT-OH3 d - - - - - -
Function
The signal OH3 is derived from a comparator with hysteresis. The switch-off threshold is 150 °Cand
is fixed. The hysteresis is also fixed and amounts to 15 K (i.e. the reclosing temperature is 135 °C.
This monitoring is only effective for the thermal sensor specified by Lenze as it is included in the
standard Lenze servo motor. The Sub-D connectors X7 or X8 serve as inputs.
Stop!
Only one of the inputs can be used. The other input must not be assigned (must remain open). This
monitoring is activated by default setting. This means that the monitoring reacts if no Lenze servo
motor is used.
Features:
•
LECOM no.: 53
•
Reaction: TRIP or OFF