Configuration
7-297
L
EDSVS9332P-D21 EN 3.0
7.6.3.3 External error EEr
Purpose
Process monitoring
MONIT
DCTRL-TRIP
MONIT- EEr
C0884/3
C0871
Fig. 7-237 External error EEr
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
DCTRL-TRIP d C0884/3 bin C0871 2 54 -
MONIT-EEr d - - - - - -
Function
The signal EEr is obtained from the signal at the input DCTRL-TRIP-SET (level evaluation). With
default setting, this signal is obtained from terminal X5/E4 . Here, external encoders can be
connected which control the controller in the desired direction.
Any other binary signal source can also be used.
Features:
•
LECOM no.: 91, 1091, 2091
•
Reaction: TRIP, MESSAGE, WARNING or OFF