7.5.21 Analog input via terminal 1,2/3,4 (AIN)
Purpose
This FB is the interface for analog signals as
setpoint input,
actual value input and
parameter control.
C0034
1
2
AIN1
+
+
AIN1-OUT
AIN1-GAIN
AIN1-OFFSET
C0404/1
C0404/2
C0402
C0403
C0400
Fig. 7-53 Analog input via terminal 1,2 (AIN1)
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
AIN1-OFFSET a C0404/1 dec [%] C0402 1 19502 -
AIN1-GAIN a C0404/2 dec [%] C0403 1 19504 -
AIN1-OUT a - - - - - -
Special feature of the input terminals 1,2
A dead travel element can be integrated into the output signal at AIN1 via code C0034.
Together with the jumper position X2 (controller front) the function 4 ... 20 mA can be
implemented as current guide value.
The signal is read cyclically (1 ms).
3
4
AIN2
+
+
AIN2-OUT
AIN2-GAIN
AIN2-OFFSET
C0409/1
C0409/2
C0407
C0408
C0405
Fig. 7-54 Analog input via terminal 3, 4 (AIN2)
Special feature of AIN2
The signal is read cyclically every 250 µs.
Signal Source Note
Name Type DIS DIS format CFG List Lenze
AIN2-OFFSET a C0409/1 dec [%] C0407 1 19503 -
AIN2-GAIN a C0409/2 dec [%] C0408 1 19505 -
AIN2-OUT a - - - - - -