Function library
7-198
L
EDSVS9332P-D21 EN 3.0
7.5.53 Free piece counter (FCNT)
Purpose
Digital up/down counter
F C N T 1 - C L K U P
C 1 1 0 2 / 1
F C N T 1 - C L K D W N
C 1 1 0 2 / 2
C 1 1 0 4 / 1
C 1 1 0 4 / 2
F C N T 1 - L D - V A L
C 1 1 0 1 / 1
C 1 1 0 3 / 1
F C N T 1 - L O A D
C 1 1 0 2 / 3
C 1 1 0 4 / 3
F C N T 1 - O U T
F C N T 1 - E Q U A L
C 1 1 0 1 / 2
C 1 1 0 3 / 2
F C N T 1 - C M P - V A L
C 1 1 0 0
C T R L
F C N T 1
Fig. 7-153 Free piece counter (FCNT1)
Signal
Source Note
Name Type DIS DIS format CFG List
FCNT1-CLKUP d C1104/1 bin C1102/1 2 LOW-HIGH edge = counts up by 1
FCNT1-CLKDWN d C1104/2 bin C1102/2 2 LOW-HIGH edge = counts down by 1
FCNT1-LD-VAL a C1103/1 dec C1101/1 1 Start value
FCNT1-LOAD d C1104/3 bin C1102/3 2
•
HIGH = Accept start value
•
The input has the highest priority
FCNT1-CMP-VAL a C1103/2 dec C1101/2 1 Comparison value
FCNT1-OUT a - - - - Counter limited to ±199.99 % (≙ ±32767)
FCNT1-EQUAL d - - - - HIGH = comparison value reached