Function library
7-265
L
EDSVS9332P-D21 EN 3.0
Negative dead time
I N x - 1 I N x - 2
S P 2 - L - I N
S P 2 - S T A T x
H I G H
L O W
T
d e a d
T
d e a d
T r a v e l d i r e c t i o n
( n e g a t i v e d e a d t i m e )
Fig. 7-218 Function of the negative dead time
With a negative dead time, the drive reacts later by the time period set.
7.5.76.4 Filter time constant
This function is available only for the FB SP2.
Purpose
Avoids undefined switching of the output signals at SP2-STAT1 ... SP2-STAT4 when the motor is
running at low speed.
Function
The filter time constant is entered via C1659.
The setting is valid for SP2-STAT1 ... SP2-STAT4.
Assignment of the codes to the filter time constant:
Code Value Filter time constant
C1659
0 Off
1 1ms
2 2ms
4 4ms
8 8ms
16 16 ms
Tip!
The correct setting can only be found by testing.
In general:
The lower the resolution of the actual position encoder and the lower the travel speed, the
higher the filter time constant.