7.6.3.19 Parameter error PRO
Purpose
Controller protection
Function
Function of LECOM no. 79 (PI)
Some parameters are used for internal calculation of further data for the servo controllers. The
monitoring reacts if incorrect values are recognized internally due to this calculation.
The cause may be:
Data of a powerful controller were transmitted to a less powerful controller, e.g. the settings of the
motors do not match with the controller.
In this case, please contact Lenze. The values of the codes C0300 and C0301 should be
communicated to Lenze.
Function of LECOM no. 75 (PR0)
This fault indication is displayed if the stored parameters do not match with the loaded software
version. In this case, the factory setting is loaded automatically. To acknowledge the PR0, all
parameter sets must be saved again manually (C0003). Only after the values have been saved, the
fault indication can be acknowledged.
Stop!
It is not sufficient to save only one parameter again.
Features:
LECOM
No.: 79 (PI)
No.: 75 (PR0)
Reaction: TRIP (cannot be modified)