Configuration
7-312
L
EDSVS9332P-D21 EN 3.0
7.6.3.17 Following error P03
Purpose
Process monitoring
MONIT
MONIT-P03
DFSET-PSET
C0255
Fig. 7-250 Following error P03
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
DFSET-PSET - - - - - - -
MONIT-P03 d - - - - - -
Function
The monitoring reacts if the drive is not able to follow its set phase, because e.g.
•
the centrifugal mass is too large for the set acceleration or deceleration time
or
•
the torque limit is reached (load torque > drive torque)
Remedy:
•
Unload drive
or
•
increase torque limit at the servo controller (if the power limits of the controller are not yet
achieved)
The monitoring is derived from the phase difference of set-value integrator minus actual phase
integrator. The comparison value (following error limit C0255) can be set by a code. Homing points
are only lost if a TRIP reaction was set.
Features:
•
to monitor the process
•
LECOM no.: 153, 2153
•
Reaction: TRIP, WARNING or OFF