EasyManua.ls Logo

Lenze 9300 - Switch on Controller

Lenze 9300
591 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
5-5
L
EDSVS9332P-C EN 3.0
5.4 Switchoncontroller
Step
1. Assign X5/28 to LOW level (CINH).
2. Connect the travel range limit switch to terminals X5/E1 and X5/E2 See: E 4-24
Assign X5/E1 and X5/E2 with HIGH level if you do not use an y travel
range limit switches.
3. Assign digital input signals to (X5/E3 ... X5/E5).
4. Switch on mains voltage. The controller is ready for operation after approx. 2 s.
5. Adapt DC-bus voltage threshold with C0173 to the mains voltage.
6. Check whether the drive is read y for operation.
When the green LED is flashing:
Controller is read y for opera tion
When green LED is o ff and red LED is flashing:
A fault has occurred. Eliminate the fault before proceeding with
commissioning. See chapter 8 ”Troubleshooting and fault
elimination”.
7. For opera tion with a fieldbus module, additional settings are
necessary.
See Operating Instructions for the corresponding fieldbus module.
Tip!
For applications with active loads (e. g. hoists) the code C0172* must be set to C0172 = 0 [Volt] to
generate an overvoltage message (OU).
As long as the overvoltage message is applied
pulse inhibit is set and
the drive has no torque.
The controller inhibit is evaluated, among other things, by the holding brake (BRK) (see chapter in
the corresponding 9300 System Manual).
*) C0172 = ”OV reduce - Threshold for activating the brake torque reduction before OU message”
Show/Hide Bookmarks

Table of Contents

Other manuals for Lenze 9300

Related product manuals