Configuration
7-318
L
EDSVS9332P-D21 EN 3.0
7.6.4 Fault indication via digital output
In the function block DIGOUT the fault messages TRIP, message and warning can be assigned to the
digital outputs (e. g. terminals X5/A1 X5/A4).
Display TRIP or Message or Warning individually (individual indication):
1. Select digital output in the code level under C0117 and subcode.
2. Assign TRIP or Message or Warning in the parameter level.
Display TRIP, Message, Warning collectively (collective indication):
1. Assign TRIP, message and warning to an OR-element.
2. Select digital output in the code level under C0117 and subcode.
3. Assign output of the OR-element in the parameter level.
Display monitoring functions individually:
1. Select digital output in the code level under C0117 and subcode.
2. Assign monitoring function (e.g. MONIT-OH7).