Function library
7-73
L
EDSVS9332P-D21 EN 3.0
7.5.11.2 Status of the program control
The actual state of the program control is displayed via the status outputs of the function block POS
and the positioning status (C1283).
Status outputs
Update conditions of the status outputs RUNNING, POS-STARTED, POS-STOPPED,
POS-ENDED, POS-RESETED and the positioning status in code C1283:
The power stage is supplied (DCTRL-RDY=1)
The drive is enabled (DCTRL-CINH=0)
No fault applies (DCTRL-TRIP=0, DCTRL-FAIL-QSP=0)
Quick stop (QSP) is not activated (MCTRL-QSP-OUT=0)
Manual operation is not activated (POS-MANUAL=0, C1280.B4=0)
9300POS027
S t a r t = L
P r o g r a m e n d
R e s e t = L , S t o p = L , S t a r t =
R e s e t = L
S t o p = H
R e s e t = L
S t o p = L
n o i n t e r r u p t i o n
R e s e t = L
P O S - V S E T = 0
R e s e t = H
S t o p = L
I n t e r r u p t i o n
R e s e t = L
S t o p = H
I n t e r r u p t i o n
R U N N I N G = 0
S T A R T E D = 0
S T O P P E D = 0
E N D E D = 1
R E S E T E D = 0
R U N N I N G = 0
S T A R T E D = 0
S T O P P E D = 0
E N D E D =
1
R E S E T E D = 1
R U N N I N G = 1
S T A R T E D = 1
S T O P P E D = 0
E N D E D = 0
R E S E T E D = 0
R U N N I N G = 0
S T A R T E D = 0
S T O P P E D = 1
E N D E D = 0
R E S E T E D = 0
R U N N I N G = 0
S T A R T E D = 1
S T O P P E D = 0
E N D E D = 0
R E S E T E D = 0
C 1 2 8 3 = " P r g R e s e t "
C 1 2 8 3 = " S t a r t e d " C 1 2 8 3 = " S t o p p e d "
C 1 2 8 3 = " S t a r t e d b r e a k "
R e s e t = L
S t o p = H
S t a r t =
R e s e t = L , S t o p = L , S t a r t =
R e s e t = H
C 1 2 8 3 = " R e a d y f o r s t a r t "
C 1 2 8 3 = " P r o g r a m e n d "
R e s e t = H
Fig. 7-33 Status machine of program control
Status Ready to start
Program control is ready to start but not started yet.
Status output POS-ENDED = HIGH,
Positioning status (C1283) = Ready to start,
Current PS No. (POS-ACT-PS-NO) = 0 (program end)
Status Started
Program has been started, the positioning program is running.
Status output POS-STARTED = HIGH and
Status output POS-RUNNING = HIGH (for firmware version
2.5)
Positioning status (C1283) = Started,
or Started-rem, if C1280.B0 = 1 (GDC control),
or Started-dig, if input POS-PRG-START = HIGH.