Installation
4-1
L
EDSVS9332P-B EN 3.0
4 Installation
4.1 Mechanical installation
4.1.1 Important notes
•
Use the controllers only as built-in devices!
•
If the cooling air contains pollutants (dust, fluff, grease, aggressive gases):
– Take suitable preventive measures , e.g. separate air duct, installation of filters, regular
cleaning, etc.
•
Observefreespace!
– You can install several controllers next to each other without free space in a control cabinet.
– Ensure unimpeded ventilation of cooling air and outlet of exhaust air!
– Allow a free space of 100 mm at the top and at the bottom.
•
Do not exceed the ambient temperature permissible during operation.
(E 3-2)
•
With continuous oscillations or vibrations:
– Check whether shock absorbers are necessary.
Possible mounting positions
Vertically on the control cabinet back panel with mains connections at the top:
•
With enclosed fixing rails or fixing brackets.
(E 4-2)
•
Thermally separated with external heatsink
–”Push-through technique”
(E 4-3)
–”Cold Plate technology”
(E 4-6)