During operation
6-3
L
EDSVS9332P-C EN 3.0
6.1.4 Actual value display via codes
You can read different actual values using the following codes:
Code Meaning
C0051 Absolute actual speed [rpm]
C0052 Absolute motor voltage [V]
C0053 Absolute DC bus voltage [V]
C0054 Absolute motor current [A]
C0060 Rotor position [Inc/rev]
C0061 Heatsink temperature [°C]
C0063 Absolute motor temperature [°C]
Display onl y if the KTY (PTC) is connected via X7 or X8.
C0064 Controller load [%]
Identification
You can read the software version of the controller under C0099.
C0093 indicates the controller type.
6.2 Information on operation
When operating the controller, please observe the following notes:
Stop!
Cyclic connection and disconnection of the controller supply voltage at L1, L2, L3 or +U
G
,
-U
G
may overload the internal input current limitation:
Allow at least 3 minutes between disconnection and reconnection.
During mains switching (L1,L2,L3) it is not important whether further controllers are supplied
via the DC bus.
6.2.1 Switching on the motor side
Switching on the motor side of the inverter is permissible for emergency switch-off.
Please note:
Switching while a controller is enabled may cause the fault message OCx
(short-circuit/earth fault in operating mode x).
For long motor cables and operation of controllers with smaller output power, leakage
currents through interfering cable capacitances may cause the fault message OCx.
Switching equipment on the motor side must be dimensioned for DC voltages
(U
DC max
= 800 V).