Installation
4-35
L
EDSVS9332P-B EN 3.0
4.2.10 Motor temperature monitoring
Selection of the sensor
type
Continuous temperature sensor KTY
“Linear” temperature sensor in the motor winding (standard for Lenze motors MDXKX, MDXQA a nd MDXMA)
PTC thermistor
PTC thermistor with defined tripping temperature (acc. to DIN 44081 and DIN 44082)
Thermal contact TKO
Thermostat/normally-closed contact
Other monitoring KTY, PTC and TKO do not offer complete protection. To improve the monitoring, Lenze recommends the use of a bimetal rel a y.
Alternative monitoring Comparators (CMP1 ... CMP3) monitor and a time element (TRANS1 ... TRANS4) limits the motor current for small speeds or motor
standstill.
This function can be implemented by interconnecting the corresponding function blocks.
Reactions different, depending on the tempera ture monitoring. E 7-291
Stop!
Do not connect an external voltage to the inputs.
Lenze motors Motors of other manufacturers
MDXKX, MDXQA and MDXMA with th ermostat with sensor for continuous
temperature detection
with thermal contact or
PTC acc. to DIN
44081/44082
Connection
Resolver input X7:
–PinX7/8=+,
Pin X7/9 = -
Encoder input X8:
–PinX8/8=+,
Pin X8/5 = -
Terminals T1/T2 next to the
terminalsU,V,W
Resolver input X7:
–PinX7/8=+,
Pin X7/9 = -
Encoder input X8:
–PinX8/8=+,
Pin X8/5 = -
Terminals T1/T2 next to the
terminalsU,V,W
Fault message (MONIT-)OH3 (MONIT-)OH7 (MONIT-)OH8 (MONIT-)OH3 (MONIT-)OH7 (MONIT-)OH8
Possible reactions
The corresponding monitoring and thus the following codes are preset under C0086
Trip
(C0583 = 0)
OFF
(C0583 = 3)
Warning (C0584
=2)
OFF
(C0584 = 3)
Trip (C0585 = 0)
Warning
(C0585 = 2)
OFF (C0585 = 3)
Trip
(C0583 = 0)
OFF
(C0583 = 3)
Warning (C0584
=2)
OFF
(C0584 = 3)
Trip (C0585 = 0)
Warning
(C0585 = 2)
OFF (C0585 = 3)
Tripping
temperature
fixed at 150 ° C adjustable
45°C ... 150°C
(C0121)
fixed, (depending on the
PTC/thermostat):
PTC: at R ϑ > 1600
fixed at 150 °C adjustable
45°C ... 150°C
(C0121)
fixed, (depending on the
PTC/thermostat):
PTC: at R ϑ > 1600
Notes
Monitoring is active in the default
setting.
If resolver (X7) and encoder (X8) are
operated together:
Connect KTY only at one connector
(X7 or X8)
Do not c onnect KTY connection of
the other female connector
For further information on the
connection of the thermal sensor,
please consult the description of the
feedback system
Deactivate monitoring
via X7 or X8 under
C0583=3 and C0584=3
Connection to DIN
44081
(see also Fig. 4-23).
Input characteristic. (E 4-36)
Deactivate monitoring via X7 or X8
under C0583=3 and C0584=3
Deactivate monitoring
via X7 or X8 under
C0583=3 and C0584=3
Connection to DIN
44081
(see also Fig. 4-23).
We reco mmend a Ziehl
PTC (up to 150 °C)
K15301075 or a
thermostat.