17
Engineer programming via the browser
Configuration
224
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
Restriction
System Option
Description
Set (FTS)
Hide bypass
If enabled, the bypass messages will no longer be
displayed on keypad.
Battery capacity
Total batteries capacity in AH, for panel only (3 - 100 Ah).
You must enter this value and Max current value to view
the remaining battery time on the keypad in the event of
mains failure. This is indicated under the STATUS -
BATTERY - BATT TIME menu.
Max current
The total current draw from batteries when mains fail
occurs (30 - 20000 mA). You must enter this value and
the Battery capacity value to view the remaining battery
time on the keypad in the event of mains failure. This is
indicated under the STATUS - BATTERY - BATT TIME
menu.
Partset
Partset A
Rename
Enter a new name for your PARTSET A mode (e.g. Night
Mode).
Partset B
Rename
Enter a new name for your PARTSET B mode (e.g. Floor
1 only).
Alarm
Bell on First
Enable to activate relevant bells/sirens on an
unconfirmed alarm. When this option is disabled, the
relevant bells/sirens will only activate on a confirmed
alarm or if the detector that caused the unconfirmed
alarm is reactivated.
Bell Retrigger
Enable to resound bells/sirens if a second zone activation
is detected (after the bell time has elapsed). If not
checked then the external bells will only trigger once.
Web Only
Alert Forbid Set
If enabled, a user cannot set an area if there is an area or
system alert present on the system.
Note: This option is only available when the Standards ->
Region selected is Switzerland or Security Grade
selected is ‘Unrestricted’.
Restore on Unset
Enable for alerts to auto clear after 30 seconds in Unset
mode.
Note: To comply with PD6662, you must disable this
option.
Antimask Set
Select the type of event reported resulting from antimask
detection when panel is Set. Options are Disabled,
Tamper, Trouble or Alarm.
The option can only be configured when the panel is in
‘Unrestricted’ mode. In Grade 2 or 3 mode, the type of
event reported is in accordance with the standards for the
selected region:
Ireland - Alarm
All other regions - Alarm
Antimask Unset
Select the type of event reported resulting from antimask
detection when panel is Unset. Options are Disabled,
Tamper, Trouble or Alarm.
The option can only be configured when the panel is in
‘Unrestricted’ mode. In Grade 2 or 3 mode, the type of
event reported is in accordance with the standards for the
selected region:
Ireland - Disabled
All other regions - Tamper
!
!
!
!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vanderbilt SPC53 Series and is the answer not in the manual?

Vanderbilt SPC53 Series Specifications

General IconGeneral
BrandVanderbilt
ModelSPC53 Series
CategoryPower Supply
LanguageEnglish

Related product manuals