Docu ment No. E ZZ024048<1>
Pr epared in October, 2021
16 / 19
No.
It e m
Nu mber of
Ch aracters
De scription
4
Log Monitor
Data 1
4
Log monitor data (Hex.) of the monitor selected with
o5-03 [Log Monitor Data 1]
5
Log Monitor
Data 2
4
Log monitor data (Hex.) of the monitor selected with
o5-04 [Log Monitor Data 2]
:
:
:
:
13
Log Monitor
Data 10
4
Log monitor data (Hex.) of the monitor selected with
o5-12 [Log Monitor Data 10]
14
Region Code
4
-
15
Encoding
data
4
Encoding data for log monitor data 1 through 10 (Hex.)
Bits 0 through 9 show the encoding of log monitor data 1 through 10. A bit value
of 1 shows that the data represents a negative value. (Log monitor data 1
through 10 is absolute value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7
have values of 1, and the encoding data = 0010010010 (Bin.) = 0092 (Hex.)
16
Row number
6
Row number (Hex.) in the data log file
o5-00: Log Type
No.
( Hex.)
Name
De scription
De fault
( Range)
o5-00
(1E81)
RUN
Logging Type
Selection
0
(0 - 1)
Selects the type of data log function. This parameter is
only available when using an LCD keypad.
0: Long Term L og
Saves data continuously over a long time period.
1: Short Term Log
Saves data of a certain time period before and after the detection of a trigger with a short
sampling cycle.
o5-01: Log Start/Stop Selection
No.
( Hex.)
Name
De scription
De fault
( Range)
o5-01
(1551)
RUN
Log Start/Stop
Selection
0
(0 - 1)
Sets the data log function. This parameter is only
available when using an LCD keypad.
0: OFF
Stops the data log.
1: ON
Starts the data log as specified by the sampling cycle set in
o5-02 [Log Sampling Interval]
.
o5-02: Log Sampling I nterval
No.
( Hex.)
Name
De scription
De fault
( Range)
o5-02
(1552)
RUN
Log Sampling
Interval
1000 ms
when
o5-00 = 0,
10 ms when
o5-00 = 1
(0 - 6000 ms)
Sets the data log sampling cycle. This parameter is only
available when using an LCD keypad.
o5-03: Log Monitor D ata 1
No.
( Hex.)
Name
De scription
De fault
( Range)
o5-03
(1553)
RUN
Log Monitor Data
1
101
(000,101 - 999)
Sets the data log monitor. This parameter is only
available when using an LCD keypad.
Note: Set the
U monitor
number you will log.
For example, to display
U1-01 [Frequency Reference]
, set
o5-03 = 101
. When it is
not necessary to set a data log monitor, set this parameter to
000
.
V / f
CL - V / f
O LV C L V A OLV
O L V / P M A O L V / P M C L V / P M
E Z O L V
V / f
CL - V / f
O LV C L V A OLV
O L V / P M A O L V / P M C L V / P M
E Z O L V
V / f
CL - V / f
O LV C L V A OLV
O L V / P M A O L V / P M C L V / P M
E Z O L V
V / f
CL - V / f
O LV C L V A OLV
O L V / P M A O L V / P M C L V / P M
E Z O L V

Table of Contents

Related product manuals